BC/BD-580FC5-B01I C
299.11 kW
Defrost: None
Product code: BC/BD-2X463CC1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 89,392 m³/h |
|---|---|
| External surface | 988.4 m² |
| Inner volume | 144.7 dm³ |
| Fin material | Aluminium |
| Net weight | 798 kg |
| Quantity | 8 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X463CC1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 174.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 298.93 | 175.39 | not rated | not rated | not rated | not rated |
| 45 | 419.90 | 298.52 | 175.77 | not rated | not rated | not rated |
| 50 | 539.87 | 418.71 | 298.18 | 176.14 | not rated | not rated |
| 55 | 659.38 | 537.98 | 417.75 | 298.00 | 176.58 | not rated |
| 60 | 778.61 | 656.75 | 536.35 | 417.08 | 298.08 | 177.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 147.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 250.68 | 148.17 | not rated | not rated | not rated | not rated |
| 45 | 350.80 | 250.28 | 148.47 | not rated | not rated | not rated |
| 50 | 450.04 | 349.74 | 249.97 | 148.78 | not rated | not rated |
| 55 | 548.87 | 448.38 | 348.90 | 249.78 | 149.17 | not rated |
| 60 | 647.46 | 546.60 | 447.02 | 348.34 | 249.86 | 149.66 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 298.928 | 51.88 | 85.8 |
| Low speed (Y) | 250.683 | 43.51 | 62.9 |
| A | 3900 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 4200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4200 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.