Skip to Content

Dry cooler BC/BD-2X463CC1-B19 C

Dry cooler BC/BD-2X463CC1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X463CC1-B19 C

Heat rejection i
298.93 kW
Air flow
89,392 m³/h
Fans
8 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,392 m³/h
External surface 988.4 m²
Inner volume 144.7 dm³
Fin materialAluminium
Net weight 798 kg
Fans
Quantity 8
Diameter 630 mm
Speed 1,330 rpm
Power 10,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X463CC1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
298.928 kW Fluid flow 51.88 m³/h Pressure drop 85.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
250.683 kW Fluid flow 43.51 m³/h Pressure drop 62.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 174.99 not rated not rated not rated not rated not rated
40 298.93 175.39 not rated not rated not rated not rated
45 419.90 298.52 175.77 not rated not rated not rated
50 539.87 418.71 298.18 176.14 not rated not rated
55 659.38 537.98 417.75 298.00 176.58 not rated
60 778.61 656.75 536.35 417.08 298.08 177.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.86 not rated not rated not rated not rated not rated
40 250.68 148.17 not rated not rated not rated not rated
45 350.80 250.28 148.47 not rated not rated not rated
50 450.04 349.74 249.97 148.78 not rated not rated
55 548.87 448.38 348.90 249.78 149.17 not rated
60 647.46 546.60 447.02 348.34 249.86 149.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 298.928 51.88 85.8
Low speed (Y) 250.683 43.51 62.9

Dimensions

Dimension drawing of BC/BD-2X463CC1-B19 C
Dimension drawing
Dimensions as drawn
A 3900 mm
B 1200 mm
C 2360 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 2310 mm
K 4200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4200 mm
Width 2360 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.