BC/BD-2x480CC5-B03 C
299.24 kW
Defrost: None
Product code: BC/BD-580FC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 86,329 m³/h |
|---|---|
| External surface | 966.0 m² |
| Inner volume | 217.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,062 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 9,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.4 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-580FC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 175.54 | not rated | not rated | not rated | not rated | not rated |
| 40 | 299.11 | 175.97 | not rated | not rated | not rated | not rated |
| 45 | 419.54 | 298.66 | 176.35 | not rated | not rated | not rated |
| 50 | 538.87 | 418.32 | 298.33 | 176.75 | not rated | not rated |
| 55 | 657.76 | 536.92 | 417.28 | 298.16 | 177.23 | not rated |
| 60 | 776.37 | 655.08 | 535.29 | 416.60 | 298.24 | 177.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 299.106 | 51.91 | 37.0 |
| A | 9100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 9400 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 9100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.