BC/BD-880DD1-B03 C
250.31 kW
Defrost: None
Product code: BC/BD-2X463CD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 62,181 m³/h |
|---|---|
| External surface | 1,235.5 m² |
| Inner volume | 170.2 dm³ |
| Fin material | Aluminium |
| Net weight | 871 kg |
| Quantity | 8 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 83.6 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X463CD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 150.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 250.32 | 150.33 | not rated | not rated | not rated | not rated |
| 45 | 347.52 | 249.77 | 150.53 | not rated | not rated | not rated |
| 50 | 443.71 | 346.31 | 249.38 | 150.82 | not rated | not rated |
| 55 | 539.41 | 441.85 | 345.36 | 249.20 | 151.24 | not rated |
| 60 | 634.86 | 536.95 | 440.39 | 344.78 | 249.32 | 151.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 250.315 | 43.41 | 43.5 |
| A | 3900 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 4200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4200 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |