Skip to Content

Dry cooler BC/BD-2x291LB1-B04 C

Dry cooler BC/BD-2x291LB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291LB1-B04 C

Heat rejection i
249.89 kW
Air flow
103,316 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 103,316 m³/h
External surface 535.8 m²
Inner volume 75.9 dm³
Fin materialAluminium
Net weight 710 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 96.6 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x291LB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
249.890 kW Fluid flow 43.37 m³/h Pressure drop 50.4 kPa
Heat rejection · Low speed (Y)
200.951 kW Fluid flow 34.88 m³/h Pressure drop 34.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 139.89 not rated not rated not rated not rated not rated
40 249.89 141.08 not rated not rated not rated not rated
45 357.60 250.50 142.12 not rated not rated not rated
50 464.57 357.71 251.05 143.05 not rated not rated
55 571.23 464.23 357.86 251.61 143.93 not rated
60 677.70 570.48 464.03 358.13 252.25 144.81

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 113.22 not rated not rated not rated not rated not rated
40 200.95 114.21 not rated not rated not rated not rated
45 286.54 201.43 115.08 not rated not rated not rated
50 371.47 286.63 201.89 115.87 not rated not rated
55 456.09 371.20 286.79 202.39 116.64 not rated
60 540.56 455.49 371.07 287.05 202.97 117.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 249.890 43.37 50.4
Low speed (Y) 200.951 34.88 34.0

Dimensions

Dimension drawing of BC/BD-2x291LB1-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.