BC/BD-2x391BD1-B04 C
498.41 kW
Defrost: None
Product code: BC/BD-2X480CC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 140,658 m³/h |
|---|---|
| External surface | 1,921.9 m² |
| Inner volume | 263.4 dm³ |
| Fin material | Aluminium |
| Net weight | 1,558 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 15,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.1 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X480CC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 293.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 498.36 | 293.68 | not rated | not rated | not rated | not rated |
| 45 | 698.20 | 497.38 | 294.21 | not rated | not rated | not rated |
| 50 | 896.30 | 695.84 | 496.59 | 294.74 | not rated | not rated |
| 55 | 1093.61 | 892.64 | 693.86 | 496.04 | 295.40 | not rated |
| 60 | 1290.43 | 1088.63 | 889.55 | 692.46 | 495.98 | 296.31 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 498.360 | 86.50 | 60.7 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 8050 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.