Skip to Content

Dry cooler BC/BD-2x491BB5-B04 C

Dry cooler BC/BD-2x491BB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x491BB5-B04 C

Heat rejection i
499.70 kW
Air flow
209,253 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 209,253 m³/h
External surface 1,218.8 m²
Inner volume 213.8 dm³
Fin materialAluminium
Net weight 1,430 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.4 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x491BB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
499.700 kW Fluid flow 86.73 m³/h Pressure drop 97.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
408.349 kW Fluid flow 70.87 m³/h Pressure drop 67.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 285.81 not rated not rated not rated not rated not rated
40 499.70 287.11 not rated not rated not rated not rated
45 709.76 500.10 288.27 not rated not rated not rated
50 918.58 709.34 500.52 289.35 not rated not rated
55 1126.88 917.37 709.07 501.03 290.44 not rated
60 1334.83 1124.89 916.44 709.06 501.75 291.63

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 235.25 not rated not rated not rated not rated not rated
40 408.35 236.33 not rated not rated not rated not rated
45 577.99 408.67 237.29 not rated not rated not rated
50 746.52 577.62 409.00 238.21 not rated not rated
55 914.51 745.47 577.40 409.47 239.16 not rated
60 1082.24 912.83 744.72 577.46 410.16 240.22

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 499.700 86.73 97.1
Low speed (Y) 408.349 70.87 67.9

Dimensions

Dimension drawing of BC/BD-2x491BB5-B04 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8050 mm
Width 2360 mm
Height 1450 mm

Downloads