Skip to Content

Dry cooler BC/BD-t-2X763AB1-B19 C

Dry cooler BC/BD-t-2X763AB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X763AB1-B19 C

Heat rejection i
499.82 kW
Air flow
158,747 m³/h
Fans
14 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 158,747 m³/h
External surface 964.5 m²
Inner volume 155.8 dm³
Fin materialAluminium
Net weight 1,065 kg
Fans
Quantity 14
Diameter 630 mm
Speed 1,330 rpm
Power 17,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X763AB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
499.817 kW Fluid flow 86.74 m³/h Pressure drop 33.6 kPa
Heat rejection · Low speed (Y)
421.409 kW Fluid flow 73.13 m³/h Pressure drop 24.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 281.75 not rated not rated not rated not rated not rated
40 499.82 284.01 not rated not rated not rated not rated
45 711.84 500.28 285.92 not rated not rated not rated
50 921.87 710.83 500.75 287.65 not rated not rated
55 1130.99 919.50 710.04 501.31 289.34 not rated
60 1339.55 1127.31 917.59 709.66 502.14 291.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 239.26 not rated not rated not rated not rated not rated
40 421.41 241.15 not rated not rated not rated not rated
45 597.86 421.67 242.73 not rated not rated not rated
50 772.35 596.80 421.91 244.17 not rated not rated
55 946.05 770.11 595.89 422.31 245.60 not rated
60 1119.24 942.65 768.26 595.45 422.99 247.09

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 499.817 86.74 33.6
Low speed (Y) 421.409 73.13 24.7

Dimensions

Dimension drawing of BC/BD-t-2X763AB1-B19 C
Dimension drawing
Dimensions as drawn
A 6750 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 6400 mm
H 900 mm
I 2260 mm
K 7100 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6750 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.