BC/BD-2X580DC5-B01 C
491.75 kW
Defrost: None
Product code: BC/BD-2X480CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 155,211 m³/h |
|---|---|
| External surface | 1,625.0 m² |
| Inner volume | 263.4 dm³ |
| Fin material | Aluminium |
| Net weight | 1,510 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X480CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 286.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 492.07 | 287.43 | not rated | not rated | not rated | not rated |
| 45 | 692.82 | 491.73 | 288.25 | not rated | not rated | not rated |
| 50 | 892.03 | 691.37 | 491.51 | 289.06 | not rated | not rated |
| 55 | 1090.50 | 889.50 | 690.21 | 491.51 | 289.98 | not rated |
| 60 | 1288.58 | 1086.95 | 887.45 | 689.52 | 491.90 | 291.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 228.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 388.06 | 228.73 | not rated | not rated | not rated | not rated |
| 45 | 543.85 | 387.59 | 229.29 | not rated | not rated | not rated |
| 50 | 698.20 | 542.35 | 387.24 | 229.89 | not rated | not rated |
| 55 | 851.96 | 695.84 | 541.22 | 387.14 | 230.56 | not rated |
| 60 | 1005.38 | 848.72 | 693.95 | 540.50 | 387.30 | 231.42 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 492.065 | 85.41 | 59.3 |
| Low speed (Y) | 388.059 | 67.34 | 38.9 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 8050 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.