Skip to Content

Dry cooler BC/BD-2X580DC5-B01 C

Dry cooler BC/BD-2X580DC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580DC5-B01 C

Heat rejection i
491.75 kW
Air flow
158,102 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 158,102 m³/h
External surface 1,324.8 m²
Inner volume 331.7 dm³
Fin materialAluminium
Net weight 1,561 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X580DC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
491.752 kW Fluid flow 85.34 m³/h Pressure drop 21.6 kPa
Heat rejection · Low speed (Y)
384.971 kW Fluid flow 66.82 m³/h Pressure drop 13.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 279.49 not rated not rated not rated not rated not rated
40 491.75 281.89 not rated not rated not rated not rated
45 698.56 493.04 284.03 not rated not rated not rated
50 903.54 698.97 494.37 286.09 not rated not rated
55 1107.72 903.19 699.60 495.83 288.13 not rated
60 1311.43 1106.59 903.21 700.65 497.62 290.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 220.87 not rated not rated not rated not rated not rated
40 384.97 222.78 not rated not rated not rated not rated
45 544.10 385.86 224.48 not rated not rated not rated
50 701.56 544.27 386.82 226.11 not rated not rated
55 858.34 701.08 544.64 387.98 227.77 not rated
60 1014.70 857.25 701.04 545.46 389.44 229.57

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 491.752 85.34 21.6
Low speed (Y) 384.971 66.82 13.9

Dimensions

Dimension drawing of BC/BD-2X580DC5-B01 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 6750 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.