Skip to Content

Dry cooler BC/BD-2X480HD5-B01 C

Dry cooler BC/BD-2X480HD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X480HD5-B01 C

Heat rejection i
365.26 kW
Air flow
118,811 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 118,811 m³/h
External surface 907.8 m²
Inner volume 166.1 dm³
Fin materialAluminium
Net weight 1,126 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X480HD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
365.262 kW Fluid flow 63.39 m³/h Pressure drop 40.0 kPa
Heat rejection · Low speed (Y)
283.875 kW Fluid flow 49.27 m³/h Pressure drop 25.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 210.15 not rated not rated not rated not rated not rated
40 365.26 211.71 not rated not rated not rated not rated
45 516.45 366.14 213.16 not rated not rated not rated
50 666.39 516.83 367.09 214.54 not rated not rated
55 815.76 666.29 517.40 368.18 215.96 not rated
60 964.79 815.23 666.57 518.30 369.53 217.49

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.66 not rated not rated not rated not rated not rated
40 283.88 165.93 not rated not rated not rated not rated
45 399.58 284.53 167.10 not rated not rated not rated
50 514.19 399.83 285.26 168.23 not rated not rated
55 628.26 514.03 400.27 286.16 169.40 not rated
60 742.08 627.81 514.25 400.99 287.28 170.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 365.262 63.39 40.0
Low speed (Y) 283.875 49.27 25.6

Dimensions

Dimension drawing of BC/BD-2X480HD5-B01 C
Dimension drawing
Dimensions as drawn
A 4750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 5250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.