BC/BD-391EC5-B04 C
183.70 kW
Defrost: None
Product code: BC/BD-2X550BB1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 70,063 m³/h |
|---|---|
| External surface | 444.5 m² |
| Inner volume | 73.6 dm³ |
| Fin material | Aluminium |
| Net weight | 567 kg |
| Quantity | 10 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 7,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.4 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X550BB1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 104.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 183.83 | 105.02 | not rated | not rated | not rated | not rated |
| 45 | 261.58 | 184.05 | 105.59 | not rated | not rated | not rated |
| 50 | 338.80 | 261.43 | 184.24 | 106.12 | not rated | not rated |
| 55 | 415.76 | 338.29 | 261.29 | 184.46 | 106.63 | not rated |
| 60 | 492.59 | 414.91 | 337.85 | 261.27 | 184.77 | 107.15 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 183.826 | 31.90 | 47.6 |
| A | 4450 mm |
|---|---|
| B | 1220 mm |
| C | 1710 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4100 mm |
| H | 800 mm |
| I | 1660 mm |
| K | 4800 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4350 mm |
|---|---|
| Width | 1800 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.