Skip to Content

Dry cooler BC/BD-2X563BD5-B19 C

Dry cooler BC/BD-2X563BD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X563BD5-B19 C

Heat rejection i
354.83 kW
Air flow
110,205 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 110,205 m³/h
External surface 972.6 m²
Inner volume 173.4 dm³
Fin materialAluminium
Net weight 881 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X563BD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
354.834 kW Fluid flow 61.59 m³/h Pressure drop 40.5 kPa
Heat rejection · Low speed (Y)
295.753 kW Fluid flow 51.33 m³/h Pressure drop 29.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 205.75 not rated not rated not rated not rated not rated
40 354.83 206.64 not rated not rated not rated not rated
45 500.05 354.68 207.41 not rated not rated not rated
50 644.02 499.01 354.59 208.14 not rated not rated
55 787.43 642.17 498.21 354.67 208.93 not rated
60 930.50 784.77 640.67 497.71 354.98 209.81

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 172.50 not rated not rated not rated not rated not rated
40 295.75 173.28 not rated not rated not rated not rated
45 415.47 295.60 173.95 not rated not rated not rated
50 534.02 414.57 295.53 174.60 not rated not rated
55 652.08 532.44 413.85 295.61 175.30 not rated
60 769.85 649.83 531.18 413.48 295.93 176.10

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 354.834 61.59 40.5
Low speed (Y) 295.753 51.33 29.3

Dimensions

Dimension drawing of BC/BD-2X563BD5-B19 C
Dimension drawing
Dimensions as drawn
A 4950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2260 mm
K 5300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.