BC/BD-580FD1-B01 C
355.17 kW
Defrost: None
Product code: BC/BD-2x680AB1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 105,415 m³/h |
|---|---|
| External surface | 1,482.6 m² |
| Inner volume | 195.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,675 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x680AB1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 208.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 355.31 | 209.01 | not rated | not rated | not rated | not rated |
| 45 | 498.71 | 355.22 | 209.69 | not rated | not rated | not rated |
| 50 | 640.93 | 497.91 | 355.24 | 210.39 | not rated | not rated |
| 55 | 782.56 | 639.44 | 497.36 | 355.48 | 211.18 | not rated |
| 60 | 923.90 | 780.40 | 638.31 | 497.16 | 356.00 | 212.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 165.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 279.75 | 166.01 | not rated | not rated | not rated | not rated |
| 45 | 390.83 | 279.48 | 166.48 | not rated | not rated | not rated |
| 50 | 500.91 | 389.97 | 279.37 | 166.99 | not rated | not rated |
| 55 | 610.51 | 499.45 | 389.35 | 279.45 | 167.58 | not rated |
| 60 | 719.84 | 608.48 | 498.36 | 389.07 | 279.80 | 168.33 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 355.310 | 61.67 | 58.9 |
| Low speed (Y) | 279.751 | 48.55 | 38.4 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 7850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.