Dry cooler BC/BD-491HC5-B04 C

Dry cooler BC/BD-491HC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-491HC5-B04 C

Heat rejection i
355.55 kW
Air flow
104,929 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 104,929 m³/h
External surface 1,059.8 m²
Inner volume 236.5 dm³
Fin materialAluminium
Net weight 1,071 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-491HC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
355.553 kW Fluid flow 61.71 m³/h Pressure drop 54.5 kPa
Heat rejection · Low speed (Y)
278.369 kW Fluid flow 48.31 m³/h Pressure drop 35.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 208.95 not rated not rated not rated not rated not rated
40 355.55 209.36 not rated not rated not rated not rated
45 498.59 354.95 209.71 not rated not rated not rated
50 640.47 497.10 354.47 210.08 not rated not rated
55 781.78 638.07 495.87 354.21 210.56 not rated
60 922.81 778.58 636.11 494.96 354.23 211.18

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 165.16 not rated not rated not rated not rated not rated
40 278.37 165.45 not rated not rated not rated not rated
45 388.53 277.83 165.72 not rated not rated not rated
50 497.72 387.32 277.45 166.05 not rated not rated
55 606.44 495.83 386.35 277.27 166.45 not rated
60 714.91 603.90 494.31 385.74 277.35 167.02

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 355.553 61.71 54.5
Low speed (Y) 278.369 48.31 35.2

Dimensions

Dimension drawing of BC/BD-491HC5-B04 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 1190 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.