BC/BD-980DB5-B01 C
389.68 kW
Defrost: None
Product code: BC/BD-2X563CD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 107,598 m³/h |
|---|---|
| External surface | 1,544.4 m² |
| Inner volume | 202.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,068 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 12,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X563CD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 224.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 390.24 | 225.78 | not rated | not rated | not rated | not rated |
| 45 | 550.60 | 390.18 | 227.04 | not rated | not rated | not rated |
| 50 | 709.19 | 549.32 | 390.12 | 228.23 | not rated | not rated |
| 55 | 866.91 | 706.77 | 548.30 | 390.34 | 229.41 | not rated |
| 60 | 1024.15 | 863.43 | 704.84 | 547.73 | 390.84 | 230.73 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 185.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 320.57 | 187.33 | not rated | not rated | not rated | not rated |
| 45 | 450.28 | 320.85 | 188.58 | not rated | not rated | not rated |
| 50 | 578.30 | 449.68 | 321.17 | 189.76 | not rated | not rated |
| 55 | 705.55 | 576.94 | 449.31 | 321.66 | 190.96 | not rated |
| 60 | 832.35 | 703.46 | 575.96 | 449.31 | 322.43 | 192.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 390.241 | 67.73 | 24.6 |
| Low speed (Y) | 320.574 | 55.59 | 17.2 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.