BC/BD-2x491EB1-B04 C
475.45 kW
Defrost: None
Product code: BC/BD-2X580DC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 150,790 m³/h |
|---|---|
| External surface | 1,324.8 m² |
| Inner volume | 331.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,561 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 19,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 94.1 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X580DC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 270.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 475.74 | 272.92 | not rated | not rated | not rated | not rated |
| 45 | 675.35 | 476.75 | 274.87 | not rated | not rated | not rated |
| 50 | 873.18 | 675.37 | 477.76 | 276.73 | not rated | not rated |
| 55 | 1070.17 | 872.32 | 675.62 | 478.92 | 278.56 | not rated |
| 60 | 1266.71 | 1068.49 | 871.88 | 676.30 | 480.39 | 280.49 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 475.735 | 82.56 | 20.4 |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 6750 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6350 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.