Skip to Content

Dry cooler BC/BD-891EB1-B04 C

Dry cooler BC/BD-891EB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-891EB1-B04 C

Heat rejection i
475.16 kW
Air flow
191,526 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 191,526 m³/h
External surface 1,153.1 m²
Inner volume 154.2 dm³
Fin materialAluminium
Net weight 1,403 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-891EB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
475.162 kW Fluid flow 82.47 m³/h Pressure drop 70.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
382.161 kW Fluid flow 66.33 m³/h Pressure drop 47.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 268.46 not rated not rated not rated not rated not rated
40 475.16 270.34 not rated not rated not rated not rated
45 677.97 476.15 272.02 not rated not rated not rated
50 879.52 678.18 477.16 273.58 not rated not rated
55 1080.53 879.03 678.60 478.25 275.12 not rated
60 1281.19 1079.31 878.89 679.27 479.53 276.71

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 217.81 not rated not rated not rated not rated not rated
40 382.16 219.33 not rated not rated not rated not rated
45 542.93 382.92 220.68 not rated not rated not rated
50 702.53 543.06 383.70 221.94 not rated not rated
55 861.63 702.08 543.35 384.59 223.23 not rated
60 1020.39 860.61 701.94 543.92 385.70 224.61

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 475.162 82.47 70.3
Low speed (Y) 382.161 66.33 47.7

Dimensions

Dimension drawing of BC/BD-891EB1-B04 C
Dimension drawing
Dimensions as drawn
A 11750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 11300 mm
H 1400 mm
I 1190 mm
K 12250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 12250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.