Skip to Content

Dry cooler BC/BD-2x580DB1-B01 C

Dry cooler BC/BD-2x580DB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580DB1-B01 C

Heat rejection i
474.69 kW
Air flow
166,564 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 166,564 m³/h
External surface 1,172.8 m²
Inner volume 264.9 dm³
Fin materialAluminium
Net weight 1,477 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.2 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x580DB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
474.694 kW Fluid flow 82.38 m³/h Pressure drop 30.0 kPa
Heat rejection · Low speed (Y)
377.090 kW Fluid flow 65.44 m³/h Pressure drop 19.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 267.72 not rated not rated not rated not rated not rated
40 474.69 270.04 not rated not rated not rated not rated
45 677.05 476.09 272.16 not rated not rated not rated
50 877.85 677.62 477.44 274.08 not rated not rated
55 1077.98 877.71 678.36 478.89 275.93 not rated
60 1277.67 1077.11 877.90 679.42 480.46 277.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 214.61 not rated not rated not rated not rated not rated
40 377.09 216.43 not rated not rated not rated not rated
45 535.33 378.09 218.08 not rated not rated not rated
50 692.17 535.63 379.09 219.58 not rated not rated
55 848.36 691.85 536.13 380.07 221.01 not rated
60 1004.16 847.46 691.91 536.74 381.20 222.54

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 474.694 82.38 30.0
Low speed (Y) 377.090 65.44 19.9

Dimensions

Dimension drawing of BC/BD-2x580DB1-B01 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 6750 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.