Skip to Content

Dry cooler BC/BD-2X580EC1-B01 C

Dry cooler BC/BD-2X580EC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580EC1-B01 C

Heat rejection i
581.79 kW
Air flow
165,306 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 165,306 m³/h
External surface 1,824.3 m²
Inner volume 376.1 dm³
Fin materialAluminium
Net weight 1,739 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.4 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X580EC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
581.788 kW Fluid flow 100.96 m³/h Pressure drop 32.8 kPa
Heat rejection · Low speed (Y)
449.996 kW Fluid flow 78.05 m³/h Pressure drop 20.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 337.84 not rated not rated not rated not rated not rated
40 581.79 339.77 not rated not rated not rated not rated
45 818.87 582.22 341.51 not rated not rated not rated
50 1053.76 818.06 582.81 343.23 not rated not rated
55 1287.60 1051.79 817.65 583.72 345.10 not rated
60 1520.80 1284.49 1050.49 817.92 585.08 347.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 264.18 not rated not rated not rated not rated not rated
40 450.00 265.61 not rated not rated not rated not rated
45 630.01 450.16 266.94 not rated not rated not rated
50 808.05 629.18 450.53 268.28 not rated not rated
55 985.16 806.29 628.75 451.20 269.69 not rated
60 1161.75 982.52 805.16 628.91 452.25 271.21

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 581.788 100.96 32.8
Low speed (Y) 449.996 78.05 20.6

Dimensions

Dimension drawing of BC/BD-2X580EC1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1400 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7550 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.