Dry cooler BC/BD-2X580EC5-B01 C

Dry cooler BC/BD-2X580EC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580EC5-B01 C

Heat rejection i
548.69 kW
Air flow
170,147 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 170,147 m³/h
External surface 1,545.6 m²
Inner volume 376.1 dm³
Fin materialAluminium
Net weight 1,693 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X580EC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
548.693 kW Fluid flow 95.23 m³/h Pressure drop 29.5 kPa
Heat rejection · Low speed (Y)
429.928 kW Fluid flow 74.61 m³/h Pressure drop 19.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 316.03 not rated not rated not rated not rated not rated
40 548.69 317.92 not rated not rated not rated not rated
45 775.45 549.21 319.60 not rated not rated not rated
50 1000.28 774.82 549.82 321.22 not rated not rated
55 1224.22 998.62 774.56 550.68 322.91 not rated
60 1447.64 1221.52 997.47 774.77 551.95 324.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 250.02 not rated not rated not rated not rated not rated
40 429.93 251.37 not rated not rated not rated not rated
45 604.60 430.05 252.58 not rated not rated not rated
50 777.63 603.72 430.29 253.77 not rated not rated
55 949.87 775.82 603.16 430.76 255.03 not rated
60 1121.64 947.14 774.49 603.04 431.54 256.47

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 548.693 95.23 29.5
Low speed (Y) 429.928 74.61 19.0

Dimensions

Dimension drawing of BC/BD-2X580EC5-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1400 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7550 mm
Width 2360 mm
Height 1450 mm

Downloads