Skip to Content

Dry cooler BC/BD-2x491BB1-B04 C

Dry cooler BC/BD-2x491BB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x491BB1-B04 C

Heat rejection i
550.66 kW
Air flow
205,745 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 205,745 m³/h
External surface 1,441.4 m²
Inner volume 213.8 dm³
Fin materialAluminium
Net weight 1,467 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x491BB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
550.655 kW Fluid flow 95.56 m³/h Pressure drop 115.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
444.181 kW Fluid flow 77.09 m³/h Pressure drop 78.8 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 316.49 not rated not rated not rated not rated not rated
40 550.66 317.84 not rated not rated not rated not rated
45 780.30 550.87 319.01 not rated not rated not rated
50 1008.48 779.49 551.16 320.13 not rated not rated
55 1235.97 1006.69 778.93 551.58 321.29 not rated
60 1463.07 1233.21 1005.28 778.71 552.28 322.58

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 257.43 not rated not rated not rated not rated not rated
40 444.18 258.48 not rated not rated not rated not rated
45 626.85 444.29 259.46 not rated not rated not rated
50 808.19 626.12 444.49 260.39 not rated not rated
55 988.90 806.66 625.66 444.90 261.40 not rated
60 1169.28 986.61 805.53 625.56 445.58 262.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 550.655 95.56 115.3
Low speed (Y) 444.181 77.09 78.8

Dimensions

Dimension drawing of BC/BD-2x491BB1-B04 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.