BC/BD-t-2X363AD5-B19 C
255.78 kW
Defrost: None
Product code: BC/BD-2X650BC1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 80,249 m³/h |
|---|---|
| External surface | 711.2 m² |
| Inner volume | 99.0 dm³ |
| Fin material | Aluminium |
| Net weight | 720 kg |
| Quantity | 12 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 8,500 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X650BC1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 148.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 255.86 | 149.32 | not rated | not rated | not rated | not rated |
| 45 | 360.40 | 255.85 | 149.89 | not rated | not rated | not rated |
| 50 | 464.10 | 359.86 | 255.91 | 150.45 | not rated | not rated |
| 55 | 567.40 | 463.05 | 359.47 | 256.08 | 151.05 | not rated |
| 60 | 670.50 | 565.86 | 462.24 | 359.33 | 256.45 | 151.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 255.855 | 44.41 | 62.4 |
| A | 5250 mm |
|---|---|
| B | 1220 mm |
| C | 1710 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4900 mm |
| H | 800 mm |
| I | 1660 mm |
| K | 5600 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5250 mm |
|---|---|
| Width | 1800 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.