Dry cooler BC/BD-t-2X363AD5-B19 C

Dry cooler BC/BD-t-2X363AD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X363AD5-B19 C

Heat rejection i
255.78 kW
Air flow
63,636 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 63,636 m³/h
External surface 583.6 m²
Inner volume 107.6 dm³
Fin materialAluminium
Net weight 554 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X363AD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
255.778 kW Fluid flow 44.36 m³/h Pressure drop 77.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
205.682 kW Fluid flow 35.67 m³/h Pressure drop 52.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 153.44 not rated not rated not rated not rated not rated
40 255.78 153.53 not rated not rated not rated not rated
45 355.08 255.00 153.60 not rated not rated not rated
50 453.34 353.52 254.36 153.75 not rated not rated
55 551.13 451.06 352.25 253.95 154.02 not rated
60 648.65 548.13 449.17 351.33 253.84 154.49

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 124.57 not rated not rated not rated not rated not rated
40 205.68 124.90 not rated not rated not rated not rated
45 284.16 205.49 125.19 not rated not rated not rated
50 361.75 283.52 205.33 125.53 not rated not rated
55 438.94 360.72 283.00 205.36 125.97 not rated
60 515.91 437.54 359.87 282.79 205.65 126.57

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 255.778 44.36 77.2
Low speed (Y) 205.682 35.67 52.5

Dimensions

Dimension drawing of BC/BD-t-2X363AD5-B19 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 2260 mm
K 3500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3150 mm
Width 2310 mm
Height 1220 mm

Downloads