BC/BD-580CB5-B01 C
257.48 kW
Defrost: None
Product code: BC/BD-2X663BB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 105,282 m³/h |
|---|---|
| External surface | 700.3 m² |
| Inner volume | 142.6 dm³ |
| Fin material | Aluminium |
| Net weight | 910 kg |
| Quantity | 12 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 7,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.4 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X663BB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 140.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 257.41 | 142.21 | not rated | not rated | not rated | not rated |
| 45 | 370.99 | 258.40 | 143.94 | not rated | not rated | not rated |
| 50 | 483.52 | 371.32 | 259.29 | 145.41 | not rated | not rated |
| 55 | 595.63 | 483.29 | 371.66 | 260.12 | 146.74 | not rated |
| 60 | 707.47 | 594.88 | 483.18 | 372.08 | 261.00 | 147.99 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 257.411 | 44.67 | 10.6 |
| A | 5850 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 5500 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 6200 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 5850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.