Skip to Content

Dry cooler BC/BD-t-2X380GB5-B01 C

Dry cooler BC/BD-t-2X380GB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X380GB5-B01 C

Heat rejection i
257.29 kW
Air flow
97,694 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 97,694 m³/h
External surface 408.5 m²
Inner volume 87.8 dm³
Fin materialAluminium
Net weight 780 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 89.6 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X380GB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
257.293 kW Fluid flow 44.66 m³/h Pressure drop 34.3 kPa
Heat rejection · Low speed (Y)
206.537 kW Fluid flow 35.85 m³/h Pressure drop 23.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.34 not rated not rated not rated not rated not rated
40 257.29 144.87 not rated not rated not rated not rated
45 368.63 258.28 146.25 not rated not rated not rated
50 479.17 369.21 259.24 147.50 not rated not rated
55 589.31 479.38 369.86 260.22 148.70 not rated
60 699.25 589.18 479.75 370.65 261.30 149.92

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 116.01 not rated not rated not rated not rated not rated
40 206.54 117.25 not rated not rated not rated not rated
45 294.60 207.29 118.37 not rated not rated not rated
50 381.89 294.99 208.02 119.40 not rated not rated
55 468.82 381.97 295.47 208.81 120.40 not rated
60 555.56 468.61 382.22 296.11 209.71 121.43

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 257.293 44.66 34.3
Low speed (Y) 206.537 35.85 23.2

Dimensions

Dimension drawing of BC/BD-t-2X380GB5-B01 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3500 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.