Skip to Content

Dry cooler BC/BD-2X680AC1-B01 C

Dry cooler BC/BD-2X680AC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X680AC1-B01 C

Heat rejection i
601.98 kW
Air flow
196,444 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 196,444 m³/h
External surface 1,976.8 m²
Inner volume 296.9 dm³
Fin materialAluminium
Net weight 1,861 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.5 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2X680AC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
601.976 kW Fluid flow 104.48 m³/h Pressure drop 15.5 kPa
Heat rejection · Low speed (Y)
475.253 kW Fluid flow 82.48 m³/h Pressure drop 10.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 332.71 not rated not rated not rated not rated not rated
40 601.98 337.02 not rated not rated not rated not rated
45 863.08 604.34 340.77 not rated not rated not rated
50 1121.62 864.10 606.60 344.19 not rated not rated
55 1378.96 1121.41 865.27 608.99 347.46 not rated
60 1635.61 1377.56 1121.63 866.88 611.63 350.74

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 265.15 not rated not rated not rated not rated not rated
40 475.25 268.67 not rated not rated not rated not rated
45 677.63 477.00 271.71 not rated not rated not rated
50 877.45 678.18 478.67 274.49 not rated not rated
55 1076.23 876.99 678.88 480.51 277.17 not rated
60 1274.37 1074.84 877.01 680.09 482.63 279.89

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 601.976 104.48 15.5
Low speed (Y) 475.253 82.48 10.1

Dimensions

Dimension drawing of BC/BD-2X680AC1-B01 C
Dimension drawing
Dimensions as drawn
A 7750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 2310 mm
K 8250 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 7750 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.