Skip to Content

Dry cooler BC/BD-t-2X763AD5-B19 C

Dry cooler BC/BD-t-2X763AD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X763AD5-B19 C

Heat rejection i
601.54 kW
Air flow
148,484 m³/h
Fans
14 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 7 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 63 — Ø630 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 19 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 148,484 m³/h
External surface 1,361.7 m²
Inner volume 217.5 dm³
Fin materialAluminium
Net weight 1,205 kg
Fans
Quantity 14
Diameter 630 mm
Speed 1,330 rpm
Power 17,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X763AD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
601.536 kW Fluid flow 104.32 m³/h Pressure drop 115.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
483.358 kW Fluid flow 83.82 m³/h Pressure drop 78.6 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 363.13 not rated not rated not rated not rated not rated
40 601.54 362.94 not rated not rated not rated not rated
45 833.17 599.46 362.90 not rated not rated not rated
50 1062.50 829.32 597.77 363.04 not rated not rated
55 1290.77 1056.96 826.15 596.62 363.46 not rated
60 1518.45 1283.58 1052.38 823.86 596.21 364.41

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 294.58 not rated not rated not rated not rated not rated
40 483.36 295.10 not rated not rated not rated not rated
45 666.31 482.71 295.55 not rated not rated not rated
50 847.34 664.68 482.18 296.15 not rated not rated
55 1027.47 844.80 663.33 482.12 297.03 not rated
60 1207.11 1024.06 842.69 662.73 482.68 298.32

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 601.536 104.32 115.9
Low speed (Y) 483.358 83.82 78.6

Dimensions

Dimension drawing of BC/BD-t-2X763AD5-B19 C
Dimension drawing
Dimensions as drawn
A 6750 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 6400 mm
H 900 mm
I 2260 mm
K 7100 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6750 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.