Skip to Content

Dry cooler BC/BD-2X680HA1-B01 C

Dry cooler BC/BD-2X680HA1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X680HA1-B01 C

Heat rejection i
368.17 kW
Air flow
221,438 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 221,438 m³/h
External surface 643.0 m²
Inner volume 125.0 dm³
Fin materialAluminium
Net weight 1,419 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X680HA1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
368.171 kW Fluid flow 63.90 m³/h Pressure drop 43.3 kPa
Heat rejection · Low speed (Y)
302.893 kW Fluid flow 52.56 m³/h Pressure drop 30.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 201.31 not rated not rated not rated not rated not rated
40 368.17 203.70 not rated not rated not rated not rated
45 532.24 370.00 205.82 not rated not rated not rated
50 695.58 533.73 371.72 207.71 not rated not rated
55 858.56 696.74 535.17 373.37 209.47 not rated
60 1021.38 859.42 697.95 536.66 375.02 211.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 166.43 not rated not rated not rated not rated not rated
40 302.89 168.38 not rated not rated not rated not rated
45 436.79 304.31 170.08 not rated not rated not rated
50 569.90 437.80 305.60 171.61 not rated not rated
55 702.71 570.58 438.80 306.85 173.05 not rated
60 835.30 703.07 571.33 439.87 308.14 174.43

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 368.171 63.90 43.3
Low speed (Y) 302.893 52.56 30.6

Dimensions

Dimension drawing of BC/BD-2X680HA1-B01 C
Dimension drawing
Dimensions as drawn
A 6850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 2260 mm
K 7350 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6850 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.