Skip to Content

Dry cooler BC/BD-2X680HB5-B01 C

Dry cooler BC/BD-2X680HB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X680HB5-B01 C

Heat rejection i
424.45 kW
Air flow
206,863 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 206,863 m³/h
External surface 817.0 m²
Inner volume 155.8 dm³
Fin materialAluminium
Net weight 1,490 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X680HB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
424.446 kW Fluid flow 73.67 m³/h Pressure drop 29.6 kPa
Heat rejection · Low speed (Y)
344.927 kW Fluid flow 59.86 m³/h Pressure drop 20.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 233.78 not rated not rated not rated not rated not rated
40 424.45 236.53 not rated not rated not rated not rated
45 611.20 426.38 238.97 not rated not rated not rated
50 796.84 612.58 428.19 241.14 not rated not rated
55 981.94 797.73 613.97 429.96 243.17 not rated
60 1166.76 982.39 798.76 615.48 431.79 245.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 190.90 not rated not rated not rated not rated not rated
40 344.93 193.19 not rated not rated not rated not rated
45 495.22 346.37 195.16 not rated not rated not rated
50 644.43 496.14 347.72 196.93 not rated not rated
55 793.14 644.86 497.08 349.08 198.61 not rated
60 941.60 793.17 645.45 498.15 350.51 200.24

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 424.446 73.67 29.6
Low speed (Y) 344.927 59.86 20.4

Dimensions

Dimension drawing of BC/BD-2X680HB5-B01 C
Dimension drawing
Dimensions as drawn
A 6850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 2260 mm
K 7350 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6850 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.