BC/BD-2x380OB1-B01 C
425.08 kW
Defrost: None
Product code: BC/BD-t-2x391OC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 132,037 m³/h |
|---|---|
| External surface | 726.2 m² |
| Inner volume | 123.8 dm³ |
| Fin material | Aluminium |
| Net weight | 966 kg |
| Quantity | 6 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 16,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2x391OC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 245.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 424.85 | 246.45 | not rated | not rated | not rated | not rated |
| 45 | 600.17 | 425.28 | 247.71 | not rated | not rated | not rated |
| 50 | 774.03 | 599.76 | 425.72 | 248.92 | not rated | not rated |
| 55 | 947.21 | 772.84 | 599.54 | 426.36 | 250.19 | not rated |
| 60 | 1119.99 | 945.25 | 771.97 | 599.69 | 427.33 | 251.62 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 424.848 | 73.74 | 68.8 |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1400 mm |
| I | 2260 mm |
| K | 4850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |