Skip to Content

Dry cooler BC/BD-2X750BD5-B09 C

Dry cooler BC/BD-2X750BD5-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X750BD5-B09 C

Heat rejection i
304.89 kW
Air flow
91,385 m³/h
Fans
14 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 91,385 m³/h
External surface 878.5 m²
Inner volume 146.4 dm³
Fin materialAluminium
Net weight 867 kg
Fans
Quantity 14
Diameter 500 mm
Speed 1,330 rpm
Power 9,900 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X750BD5-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
304.889 kW Fluid flow 52.91 m³/h Pressure drop 64.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 179.19 not rated not rated not rated not rated not rated
40 304.89 179.76 not rated not rated not rated not rated
45 427.49 304.72 180.26 not rated not rated not rated
50 549.08 426.68 304.64 180.79 not rated not rated
55 670.21 547.67 426.10 304.73 181.38 not rated
60 791.03 668.19 546.57 425.82 305.08 182.14

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 304.889 52.91 64.9

Dimensions

Dimension drawing of BC/BD-2X750BD5-B09 C
Dimension drawing
Dimensions as drawn
A 6050 mm
B 1220 mm
C 1710 mm
F 1050 mm
G 450 mm
E 5700 mm
H 800 mm
I 1660 mm
K 6400 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6050 mm
Width 1800 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.