BC/BD-t-2X580GC1-B01 C
505.83 kW
Defrost: None
Product code: BC/BD-2X763BD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 154,287 m³/h |
|---|---|
| External surface | 1,361.7 m² |
| Inner volume | 217.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,205 kg |
| Quantity | 14 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 17,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X763BD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 298.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 505.84 | 298.70 | not rated | not rated | not rated | not rated |
| 45 | 708.68 | 505.08 | 299.16 | not rated | not rated | not rated |
| 50 | 909.96 | 706.81 | 504.52 | 299.67 | not rated | not rated |
| 55 | 1110.51 | 906.98 | 705.26 | 504.22 | 300.31 | not rated |
| 60 | 1310.66 | 1106.46 | 904.52 | 704.25 | 504.32 | 301.18 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 249.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 421.30 | 250.31 | not rated | not rated | not rated | not rated |
| 45 | 588.43 | 420.65 | 250.73 | not rated | not rated | not rated |
| 50 | 754.11 | 586.78 | 420.15 | 251.18 | not rated | not rated |
| 55 | 919.21 | 751.59 | 585.50 | 419.96 | 251.77 | not rated |
| 60 | 1083.93 | 915.77 | 749.57 | 584.69 | 420.07 | 252.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 505.842 | 87.79 | 102.9 |
| Low speed (Y) | 421.301 | 73.11 | 74.4 |
| A | 6750 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 7100 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6750 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.