BC/BD-2X580AC1-B01I C
507.19 kW
Defrost: None
Product code: BC/BD-791ED1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 147,910 m³/h |
|---|---|
| External surface | 1,681.7 m² |
| Inner volume | 208.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,425 kg |
| Quantity | 7 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 19,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.5 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-791ED1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 290.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 506.73 | 293.05 | not rated | not rated | not rated | not rated |
| 45 | 716.40 | 507.62 | 294.96 | not rated | not rated | not rated |
| 50 | 923.96 | 716.26 | 508.47 | 296.83 | not rated | not rated |
| 55 | 1130.62 | 922.87 | 716.20 | 509.58 | 298.72 | not rated |
| 60 | 1336.75 | 1128.64 | 922.10 | 716.72 | 511.08 | 300.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 506.727 | 87.95 | 31.7 |
| A | 10350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9900 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 10850 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.