BC/BD-2X680CC5-B01 C
723.58 kW
Defrost: None
Product code: BC/BD-2X780DC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 204,806 m³/h |
|---|---|
| External surface | 2,189.2 m² |
| Inner volume | 466.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,206 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 27,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.6 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X780DC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 424.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 723.42 | 425.96 | not rated | not rated | not rated | not rated |
| 45 | 1014.77 | 723.61 | 427.66 | not rated | not rated | not rated |
| 50 | 1303.62 | 1013.60 | 724.07 | 429.45 | not rated | not rated |
| 55 | 1591.27 | 1301.14 | 1012.95 | 724.98 | 431.39 | not rated |
| 60 | 1878.20 | 1587.49 | 1299.50 | 1013.16 | 726.46 | 433.70 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 723.423 | 125.57 | 49.2 |
| A | 8950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 9450 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 8950 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.