Skip to Content

Dry cooler BC/BD-2x591DB1-B04 C

Dry cooler BC/BD-2x591DB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x591DB1-B04 C

Heat rejection i
720.33 kW
Air flow
247,016 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 247,016 m³/h
External surface 1,710.3 m²
Inner volume 356.7 dm³
Fin materialAluminium
Net weight 1,855 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 101.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x591DB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
720.328 kW Fluid flow 125.02 m³/h Pressure drop 86.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
568.120 kW Fluid flow 98.60 m³/h Pressure drop 56.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 415.92 not rated not rated not rated not rated not rated
40 720.33 417.67 not rated not rated not rated not rated
45 1018.38 720.61 419.25 not rated not rated not rated
50 1314.37 1017.32 721.01 420.80 not rated not rated
55 1609.36 1312.03 1016.63 721.69 422.47 not rated
60 1903.81 1605.76 1310.29 1016.51 722.79 424.26

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 331.06 not rated not rated not rated not rated not rated
40 568.12 332.39 not rated not rated not rated not rated
45 799.62 568.23 333.63 not rated not rated not rated
50 1029.29 798.67 568.49 334.90 not rated not rated
55 1258.11 1027.30 798.06 569.08 336.27 not rated
60 1486.45 1255.11 1025.87 798.01 570.08 337.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 720.328 125.02 86.4
Low speed (Y) 568.120 98.60 56.5

Dimensions

Dimension drawing of BC/BD-2x591DB1-B04 C
Dimension drawing
Dimensions as drawn
A 9300 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9800 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9800 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.