BC/BD-2X880AC1-B01I C
797.35 kW
Defrost: None
Product code: BC/BD-2X780EC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 219,530 m³/h |
|---|---|
| External surface | 2,554.1 m² |
| Inner volume | 528.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,401 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 27,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 95.3 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X780EC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 473.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 798.94 | 474.27 | not rated | not rated | not rated | not rated |
| 45 | 1116.21 | 798.06 | 475.33 | not rated | not rated | not rated |
| 50 | 1430.80 | 1113.57 | 797.41 | 476.54 | not rated | not rated |
| 55 | 1744.04 | 1426.43 | 1111.59 | 797.42 | 477.98 | not rated |
| 60 | 2056.55 | 1738.03 | 1423.09 | 1110.56 | 798.23 | 479.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 798.935 | 138.65 | 67.1 |
| A | 10350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9900 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 10850 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 10350 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.