BC/BD-2X880AC1-B01I C
797.35 kW
Defrost: None
Product code: BC/BD-2x691EC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 269,436 m³/h |
|---|---|
| External surface | 2,306.3 m² |
| Inner volume | 331.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,082 kg |
| Quantity | 12 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 33,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 102.8 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2x691EC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 444.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 795.19 | 449.09 | not rated | not rated | not rated | not rated |
| 45 | 1136.69 | 797.36 | 452.91 | not rated | not rated | not rated |
| 50 | 1475.36 | 1137.12 | 799.45 | 456.46 | not rated | not rated |
| 55 | 1812.64 | 1474.17 | 1137.82 | 801.71 | 459.86 | not rated |
| 60 | 2149.20 | 1809.93 | 1473.59 | 1139.12 | 804.35 | 463.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 795.188 | 138.02 | 28.8 |
| A | 8950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 9450 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 9450 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.