BC/BD-2x880DB1-B01 C
742.04 kW
Defrost: None
Product code: BC/BD-2X880AC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 255,254 m³/h |
|---|---|
| External surface | 2,228.6 m² |
| Inner volume | 365.0 dm³ |
| Fin material | Aluminium |
| Net weight | 2,386 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 31,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X880AC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 419.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 741.60 | 422.72 | not rated | not rated | not rated | not rated |
| 45 | 1056.05 | 743.10 | 425.67 | not rated | not rated | not rated |
| 50 | 1368.01 | 1056.02 | 744.58 | 428.42 | not rated | not rated |
| 55 | 1678.77 | 1366.56 | 1056.26 | 746.22 | 431.11 | not rated |
| 60 | 1988.88 | 1675.98 | 1365.67 | 1057.01 | 748.24 | 433.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 741.604 | 128.72 | 28.1 |
| A | 10150 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 10650 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 10150 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.