BC/BD-2X980AC1-B01I C
905.56 kW
Defrost: None
Product code: BC/BD-2X880EC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 272,236 m³/h |
|---|---|
| External surface | 2,473.0 m² |
| Inner volume | 590.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,659 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X880EC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 532.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 902.41 | 533.52 | not rated | not rated | not rated | not rated |
| 45 | 1264.26 | 901.95 | 534.78 | not rated | not rated | not rated |
| 50 | 1623.31 | 1262.11 | 901.79 | 536.17 | not rated | not rated |
| 55 | 1981.07 | 1619.58 | 1260.65 | 902.18 | 537.84 | not rated |
| 60 | 2338.07 | 1975.80 | 1616.93 | 1260.18 | 903.40 | 540.01 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 420.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 705.84 | 420.96 | not rated | not rated | not rated | not rated |
| 45 | 984.27 | 704.97 | 421.72 | not rated | not rated | not rated |
| 50 | 1260.44 | 981.98 | 704.36 | 422.66 | not rated | not rated |
| 55 | 1535.49 | 1256.74 | 980.30 | 704.37 | 423.84 | not rated |
| 60 | 1809.94 | 1530.44 | 1253.95 | 979.48 | 705.09 | 425.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 902.411 | 156.61 | 93.8 |
| Low speed (Y) | 705.839 | 122.51 | 60.6 |
| A | 11750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 11300 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 12250 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11750 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.