Skip to Content

Dry cooler BC/BD-2X880EC5-B01 C

Dry cooler BC/BD-2X880EC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X880EC5-B01 C

Heat rejection i
902.41 kW
Air flow
272,236 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 272,236 m³/h
External surface 2,473.0 m²
Inner volume 590.7 dm³
Fin materialAluminium
Net weight 2,659 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2X880EC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
902.411 kW Fluid flow 156.61 m³/h Pressure drop 93.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
705.839 kW Fluid flow 122.51 m³/h Pressure drop 60.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 532.19 not rated not rated not rated not rated not rated
40 902.41 533.52 not rated not rated not rated not rated
45 1264.26 901.95 534.78 not rated not rated not rated
50 1623.31 1262.11 901.79 536.17 not rated not rated
55 1981.07 1619.58 1260.65 902.18 537.84 not rated
60 2338.07 1975.80 1616.93 1260.18 903.40 540.01

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 420.21 not rated not rated not rated not rated not rated
40 705.84 420.96 not rated not rated not rated not rated
45 984.27 704.97 421.72 not rated not rated not rated
50 1260.44 981.98 704.36 422.66 not rated not rated
55 1535.49 1256.74 980.30 704.37 423.84 not rated
60 1809.94 1530.44 1253.95 979.48 705.09 425.48

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 902.411 156.61 93.8
Low speed (Y) 705.839 122.51 60.6

Dimensions

Dimension drawing of BC/BD-2X880EC5-B01 C
Dimension drawing
Dimensions as drawn
A 11750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 11300 mm
H 1400 mm
I 2310 mm
K 12250 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11750 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.