BC/BD-2X880EC5-B01 C
902.41 kW
Defrost: None
Product code: BC/BD-2X980AC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 279,892 m³/h |
|---|---|
| External surface | 2,965.2 m² |
| Inner volume | 399.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,749 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 35,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 97.5 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X980AC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 520.22 | not rated | not rated | not rated | not rated | not rated |
| 40 | 905.56 | 523.49 | not rated | not rated | not rated | not rated |
| 45 | 1281.00 | 906.49 | 526.38 | not rated | not rated | not rated |
| 50 | 1653.22 | 1280.05 | 907.55 | 529.13 | not rated | not rated |
| 55 | 2023.91 | 1650.44 | 1279.54 | 909.02 | 531.96 | not rated |
| 60 | 2393.78 | 2019.37 | 1648.52 | 1279.84 | 911.06 | 535.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 905.562 | 157.17 | 44.2 |
| A | 11350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10900 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 11850 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11350 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.