BC/BD-t-2X180GA1-B01 C
75.78 kW
Defrost: None
Product code: BC/BD-2x180MB1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,163 m³/h |
|---|---|
| External surface | 367.4 m² |
| Inner volume | 45.7 dm³ |
| Fin material | Aluminium |
| Net weight | 436 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-2x180MB1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 45.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 75.86 | 45.32 | not rated | not rated | not rated | not rated |
| 45 | 105.61 | 75.60 | 45.30 | not rated | not rated | not rated |
| 50 | 135.13 | 105.14 | 75.38 | 45.29 | not rated | not rated |
| 55 | 164.53 | 134.45 | 104.74 | 75.20 | 45.31 | not rated |
| 60 | 193.86 | 163.65 | 133.87 | 104.42 | 75.11 | 45.38 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 36.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 60.70 | 36.49 | not rated | not rated | not rated | not rated |
| 45 | 84.23 | 60.46 | 36.42 | not rated | not rated | not rated |
| 50 | 107.56 | 83.81 | 60.18 | 36.36 | not rated | not rated |
| 55 | 130.78 | 106.96 | 83.35 | 59.95 | 36.32 | not rated |
| 60 | 153.96 | 130.01 | 106.31 | 82.96 | 59.78 | 36.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 75.860 | 13.16 | 78.9 |
| Low speed (Y) | 60.698 | 10.53 | 53.0 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2260 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.