Dry cooler BC/BD-t-2X180GA1-B01 C

Dry cooler BC/BD-t-2X180GA1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X180GA1-B01 C

Heat rejection i
75.78 kW
Air flow
35,148 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 35,148 m³/h
External surface 107.2 m²
Inner volume 20.8 dm³
Fin materialAluminium
Net weight 295 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-t-2X180GA1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
75.780 kW Fluid flow 13.15 m³/h Pressure drop 65.9 kPa
Heat rejection · Low speed (Y)
62.104 kW Fluid flow 10.78 m³/h Pressure drop 46.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 41.84 not rated not rated not rated not rated not rated
40 75.78 42.27 not rated not rated not rated not rated
45 109.11 76.08 42.66 not rated not rated not rated
50 142.27 109.31 76.37 43.01 not rated not rated
55 175.33 142.36 109.51 76.65 43.34 not rated
60 208.34 175.33 142.48 109.73 76.94 43.68

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 34.54 not rated not rated not rated not rated not rated
40 62.10 34.88 not rated not rated not rated not rated
45 89.10 62.32 35.19 not rated not rated not rated
50 115.91 89.21 62.53 35.47 not rated not rated
55 142.64 115.92 89.33 62.73 35.74 not rated
60 169.32 142.56 115.97 89.48 62.96 36.01

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 75.780 13.15 65.9
Low speed (Y) 62.104 10.78 46.3

Dimensions

Dimension drawing of BC/BD-t-2X180GA1-B01 C
Dimension drawing
Dimensions as drawn
A 1400 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1150 mm
H 1050 mm
I 2260 mm
K 1700 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 1400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.