Skip to Content

Dry cooler BC/BD-2x280HD5-B03 C

Dry cooler BC/BD-2x280HD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280HD5-B03 C

Heat rejection i
110.52 kW
Air flow
29,421 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 29,421 m³/h
External surface 453.9 m²
Inner volume 61.9 dm³
Fin materialAluminium
Net weight 600 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x280HD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
110.520 kW Fluid flow 19.17 m³/h Pressure drop 64.7 kPa
Heat rejection · Low speed (Y)
82.597 kW Fluid flow 14.33 m³/h Pressure drop 38.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 66.12 not rated not rated not rated not rated not rated
40 110.52 66.36 not rated not rated not rated not rated
45 153.72 110.56 66.60 not rated not rated not rated
50 196.52 153.59 110.66 66.87 not rated not rated
55 239.13 196.24 153.58 110.84 67.19 not rated
60 281.65 238.72 196.14 153.72 111.16 67.58

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 49.87 not rated not rated not rated not rated not rated
40 82.60 50.08 not rated not rated not rated not rated
45 114.33 82.65 50.29 not rated not rated not rated
50 145.75 114.27 82.75 50.52 not rated not rated
55 177.02 145.59 114.30 82.93 50.78 not rated
60 208.21 176.76 145.56 114.47 83.23 51.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 110.520 19.17 64.7
Low speed (Y) 82.597 14.33 38.4

Dimensions

Dimension drawing of BC/BD-2x280HD5-B03 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.