BC/BD-363CC1-B19 C
110.05 kW
Defrost: None
Product code: BC/BD-t-363AB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 34,129 m³/h |
|---|---|
| External surface | 209.4 m² |
| Inner volume | 29.8 dm³ |
| Fin material | Aluminium |
| Net weight | 293 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-363AB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 63.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 110.23 | 63.75 | not rated | not rated | not rated | not rated |
| 45 | 155.83 | 110.18 | 64.00 | not rated | not rated | not rated |
| 50 | 201.03 | 155.48 | 110.15 | 64.24 | not rated | not rated |
| 55 | 246.06 | 200.41 | 155.20 | 110.17 | 64.48 | not rated |
| 60 | 290.99 | 245.16 | 199.89 | 155.02 | 110.26 | 64.77 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 53.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.85 | 54.08 | not rated | not rated | not rated | not rated |
| 45 | 130.76 | 92.77 | 54.28 | not rated | not rated | not rated |
| 50 | 168.31 | 130.41 | 92.72 | 54.47 | not rated | not rated |
| 55 | 205.70 | 167.73 | 130.15 | 92.71 | 54.68 | not rated |
| 60 | 243.00 | 204.88 | 167.25 | 129.96 | 92.78 | 54.92 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 110.232 | 19.13 | 65.9 |
| Low speed (Y) | 92.845 | 16.11 | 48.7 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 3300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.