Skip to Content

Dry cooler BC/BD-363CC1-B19 C

Dry cooler BC/BD-363CC1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-363CC1-B19 C

Heat rejection i
110.05 kW
Air flow
33,522 m³/h
Fans
3 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 33,522 m³/h
External surface 370.7 m²
Inner volume 44.1 dm³
Fin materialAluminium
Net weight 357 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-363CC1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
110.045 kW Fluid flow 19.10 m³/h Pressure drop 47.7 kPa
Heat rejection · Low speed (Y)
92.368 kW Fluid flow 16.03 m³/h Pressure drop 34.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 63.39 not rated not rated not rated not rated not rated
40 110.05 63.69 not rated not rated not rated not rated
45 155.50 110.00 63.95 not rated not rated not rated
50 200.55 155.16 109.98 64.19 not rated not rated
55 245.42 199.93 154.88 110.00 64.45 not rated
60 290.17 244.50 199.41 154.70 110.10 64.74

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 53.61 not rated not rated not rated not rated not rated
40 92.37 53.86 not rated not rated not rated not rated
45 130.00 92.32 54.07 not rated not rated not rated
50 167.28 129.70 92.28 54.28 not rated not rated
55 204.39 166.73 129.45 92.30 54.50 not rated
60 241.40 203.61 166.29 129.30 92.37 54.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 110.045 19.10 47.7
Low speed (Y) 92.368 16.03 34.8

Dimensions

Dimension drawing of BC/BD-363CC1-B19 C
Dimension drawing
Dimensions as drawn
A 3000 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 1190 mm
K 3300 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3300 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.