BC/BD-2X263CC5-B01 C
109.94 kW
Defrost: None
Product code: BC/BD-380KC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 28,653 m³/h |
|---|---|
| External surface | 542.8 m² |
| Inner volume | 57.2 dm³ |
| Fin material | Aluminium |
| Net weight | 591 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-380KC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 65.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 109.91 | 65.55 | not rated | not rated | not rated | not rated |
| 45 | 153.04 | 109.65 | 65.66 | not rated | not rated | not rated |
| 50 | 195.73 | 152.47 | 109.45 | 65.79 | not rated | not rated |
| 55 | 238.22 | 194.86 | 152.00 | 109.32 | 65.95 | not rated |
| 60 | 280.60 | 237.07 | 194.15 | 151.67 | 109.31 | 66.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 50.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 84.48 | 50.78 | not rated | not rated | not rated | not rated |
| 45 | 117.13 | 84.25 | 50.86 | not rated | not rated | not rated |
| 50 | 149.41 | 116.64 | 84.06 | 50.96 | not rated | not rated |
| 55 | 181.52 | 148.68 | 116.23 | 83.95 | 51.08 | not rated |
| 60 | 213.55 | 180.56 | 148.07 | 115.96 | 83.93 | 51.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 109.905 | 19.06 | 39.3 |
| Low speed (Y) | 84.483 | 14.65 | 24.4 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.