Skip to Content

Dry cooler BC/BD-563CA5-B19 C

Dry cooler BC/BD-563CA5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-563CA5-B19 C

Heat rejection i
109.60 kW
Air flow
61,088 m³/h
Fans
5 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 61,088 m³/h
External surface 261.2 m²
Inner volume 45.4 dm³
Fin materialAluminium
Net weight 467 kg
Fans
Quantity 5
Diameter 630 mm
Speed 1,330 rpm
Power 6,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-563CA5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
109.599 kW Fluid flow 19.02 m³/h Pressure drop 30.3 kPa
Heat rejection · Low speed (Y)
96.715 kW Fluid flow 16.79 m³/h Pressure drop 24.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 60.32 not rated not rated not rated not rated not rated
40 109.60 60.87 not rated not rated not rated not rated
45 158.08 109.92 61.35 not rated not rated not rated
50 206.33 158.21 110.20 61.77 not rated not rated
55 254.48 206.27 158.32 110.47 62.15 not rated
60 302.56 254.23 206.21 158.44 110.74 62.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 53.42 not rated not rated not rated not rated not rated
40 96.72 53.92 not rated not rated not rated not rated
45 139.23 96.99 54.35 not rated not rated not rated
50 181.50 139.33 97.24 54.73 not rated not rated
55 223.68 181.44 139.42 97.48 55.08 not rated
60 265.80 223.46 181.40 139.54 97.73 55.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 109.599 19.02 30.3
Low speed (Y) 96.715 16.79 24.3

Dimensions

Dimension drawing of BC/BD-563CA5-B19 C
Dimension drawing
Dimensions as drawn
A 4800 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 1190 mm
K 5100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5100 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.