Skip to Content

Dry cooler BC/BD-2X280HA5-B01 C

Dry cooler BC/BD-2X280HA5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X280HA5-B01 C

Heat rejection i
109.33 kW
Air flow
75,540 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 75,540 m³/h
External surface 181.6 m²
Inner volume 45.0 dm³
Fin materialAluminium
Net weight 516 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.2 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2X280HA5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
109.328 kW Fluid flow 18.98 m³/h Pressure drop 38.1 kPa
Heat rejection · Low speed (Y)
90.429 kW Fluid flow 15.69 m³/h Pressure drop 27.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 59.70 not rated not rated not rated not rated not rated
40 109.33 60.42 not rated not rated not rated not rated
45 158.13 109.90 61.04 not rated not rated not rated
50 206.74 158.60 110.42 61.61 not rated not rated
55 255.23 207.12 159.05 110.91 62.12 not rated
60 303.68 255.54 207.51 159.50 111.38 62.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 49.57 not rated not rated not rated not rated not rated
40 90.43 50.17 not rated not rated not rated not rated
45 130.52 90.87 50.68 not rated not rated not rated
50 170.41 130.86 91.27 51.15 not rated not rated
55 210.19 170.65 131.18 91.65 51.57 not rated
60 249.93 210.35 170.91 131.52 92.03 51.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 109.328 18.98 38.1
Low speed (Y) 90.429 15.69 27.2

Dimensions

Dimension drawing of BC/BD-2X280HA5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.