BC/BD-2x180KB1-B01 C
109.08 kW
Defrost: None
Product code: BC/BD-550DD5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 32,255 m³/h |
|---|---|
| External surface | 414.6 m² |
| Inner volume | 61.0 dm³ |
| Fin material | Aluminium |
| Net weight | 435 kg |
| Quantity | 5 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-550DD5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 61.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 109.19 | 62.24 | not rated | not rated | not rated | not rated |
| 45 | 155.12 | 109.37 | 62.77 | not rated | not rated | not rated |
| 50 | 200.51 | 154.99 | 109.55 | 63.24 | not rated | not rated |
| 55 | 245.68 | 200.10 | 154.90 | 109.77 | 63.71 | not rated |
| 60 | 290.72 | 245.01 | 199.80 | 154.93 | 110.06 | 64.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 109.185 | 18.95 | 10.9 |
| A | 4300 mm |
|---|---|
| B | 1200 mm |
| C | 920 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4100 mm |
| H | 800 mm |
| I | 870 mm |
| K | 4600 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4600 mm |
|---|---|
| Width | 920 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.