BC/BD-380HD1-B01 C
147.82 kW
Defrost: None
Product code: BC/BD-2x280KC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 38,049 m³/h |
|---|---|
| External surface | 714.4 m² |
| Inner volume | 86.7 dm³ |
| Fin material | Aluminium |
| Net weight | 721 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x280KC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.54 | 88.91 | not rated | not rated | not rated | not rated |
| 45 | 204.60 | 147.09 | 88.92 | not rated | not rated | not rated |
| 50 | 261.13 | 203.75 | 146.73 | 88.97 | not rated | not rated |
| 55 | 317.42 | 259.91 | 203.06 | 146.49 | 89.05 | not rated |
| 60 | 373.58 | 315.83 | 258.90 | 202.56 | 146.41 | 89.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 68.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 113.32 | 68.83 | not rated | not rated | not rated | not rated |
| 45 | 156.47 | 112.92 | 68.81 | not rated | not rated | not rated |
| 50 | 199.20 | 155.75 | 112.59 | 68.83 | not rated | not rated |
| 55 | 241.74 | 198.18 | 155.16 | 112.38 | 68.92 | not rated |
| 60 | 284.17 | 240.41 | 197.33 | 154.74 | 112.31 | 69.09 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 147.539 | 25.59 | 71.8 |
| Low speed (Y) | 113.319 | 19.65 | 44.9 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 4150 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.